We recently discovered that we incorrectly sized a motor for a Model D35EKSTNNECA Hydra-Cell Pro pump system and our mistake was related to our customer using a variable frequency drive (VFD) to operate within a 3.4 to 20 GPM flow range at pressures up to 1200 PSIG. We are sharing this experience to help others avoid the same mistake and to explain how we resolved it.
Wanner Engineering provides the following formula to calculate the
Horsepower (HP) needed for a given flow rate and pressure for the model D35
pump:
The maximum discharge pressure for our customers application is 1200 PSI. Next, we need to determine the values for RPM and GPM for both the high and low ends of the flow range; the formula for this calculation is:
We input (3) variables to calculate the 4th variable. Continuing with
our example, our customer wanted to direct-drive the pump, thus connecting
the motor shaft to the pump shaft with a coupling. They intend to use a VFD
to reduce the pump/motor shaft RPM to operate within a flow range of 3.4 GPM
to 20 GPM.
The two constants for the formula above are Rated GPM and Rated RPM, a
reference to the pump flow rate at a specific RPM. Per the D35 “E” CAM, the
rated GPM = 34 and the rated RPM=1150.
Next, we input one variable and solve for the other; since we know the
customers desired flow range, we input the Target GPM and solve for the
Target RPM (the RPM required for the desired flow rate).
Using the low end of the desired flow rate, the RPM required for 3.4 GPM
with the D35 “E” CAM pump is 115:
When you solve for Target GPM=20, the Target or required operating RPM =
676.5.
Returning to the Horsepower formula and substituting the Target GPM and
RPM into it for calculating Horsepower
required based on flow and
pressure:
3.4 GPM @ 1200 PSIG requires 2.98 HP
20 GPM @ 1200 PSIG requires 17.5 HP
So, use a 20 HP motor, right?
WRONG!
The problem
is related to shaft torque, because even
though most motors are designed to provide constant torque throughout a 10:1
turndown ratio, that “constant torque” or “maximum torque” is based upon the
motors rated or maximum RPM; and our customer will be operating at less than
the maximum RPM.
Calculating Torque
The maximum amount of torque a
motor can output in inch-lbs units is calculated with the formula:
Thus, if we plug-in “20” for HP and “1150” for RPM (the maximum rated motor
RPM in our example) the result is 1096 inch-lbs of torque is the maximum
amount of torque available from a standard motor; AND the motor can maintain
that torque across a 10:1 turndown, so from 115 to 1150 RPM.
Is 1096 inch-lbs torque enough?
To determine this, we need to calculate the torque required for the application and thus we need to use 115 RPM (lowest desired operating RPM) into the torque formula above.
The result of 1643 inch-lbs is required when operating at 115 RPM and
since that exceeds the 1095 inch-lbs torque limit of a 20 HP motor, a higher
HP motor is necessary. Always use the lowest RPM to determine the worst-case
scenario for Torque required.
We can calculate the horsepower required for a specific torque
requirement. Since this application requires 1643 inch-lbs torque, we
substitute the torque and RPM variables, solving for HP:
The result? 30 HP is required to deliver 1643 inch-lbs of shaft torque which can be maintained across the 10:1 turndown capability of standard motors. Thus, our customer requires a 30 HP motor if they direct drive the pump and use a VFD for flow control.
Torque Vs. Horsepower
Torque is the rotational force
required to overcome resistance and for a Hydra-Cell Pro Pump application,
the
“resistance” is restriction to flow or operating pressure.
Wanner Engineering’s Horsepower formula is related to the rotational
velocity (RPM) required for liquid displacement. When not operating at the
motors maximum RPM you need to also check the shaft torque required and
determine the HP required to deliver that much torque as it will exceed the
rotational HP required and ultimately determine the HP required.
RPM is a variable for calculating both torque and rotational horsepower;
however, a decrease in RPM lowers horsepower and increases torque.
Problem
When our customer attempted to operate their
pump at high pressure and at a reduced RPM, their VFD automatically shut
down due to an increase in amperage. This occurs because, with a constant
torque load, the motor must maintain torque at lower speeds, causing
amperage to remain steady or slightly increase as horsepower decreases.
Eventually, this can exceed the VFD’s current limit and trigger a shutdown.
Our customer’s system is designed for a 20 HP motor, so they bought a 20 HP
VFD, their electrical wiring is rated for 20 HP and the physical space
allotted for the pump system is based upon the 20 HP motor size. Increasing
the motor to 30 HP would be expensive for both us and our customer; at a
minimum we would be responsible for a new motor, baseplate, coupling and
VFD.
Solution
Delivering 20 GPM at 1200 PSIG requires
approximately 1630 inch-lbs of shaft torque BECAUSE we are operating the
motor shaft at LESS than maximum RPM, but what if we could operate at
maximum (1150) RPM and deliver only 20 GPM?
Yes, that is the solution! Mechanically reduce the pump shaft speed and
let the motor run at full speed. The simplest and most acceptable solution
for our customer was switching from direct-drive to a belt-driven
configuration. Other potential solutions were to use a 900 RPM motor or
install a gearbox, but those would have been more costly options and the
associated lead time significantly longer.
Calculating the sheave/pulley diameter and belt length required can be covered in a separate article; Wanner Engineering was very helpful in this regard.
The parts required were a different baseplate with a belt guard,
adjustable motor mount, shaft sheaves and belts. The overall footprint was
similar and some plumbing modifications were required; all of the electrical
aspects of their system did not need to be modified.
Automating Calculations
Wanner Engineering provides
a spreadsheet to quickly determine the horsepower required within the
Technical Information\Calculation Tools section of the Partners Portal. This
spreadsheet automates both the calculation for horsepower required for flow
and pressure as well as the horsepower required to maintain torque at
reduced RPM. However, it is limited to only 6 pump models and you still need
to calculate the operating RPM required, which varies amongst a given pump
model due to multiple CAM/displacement options. Therefore, with this
experience fresh in-mind, we created an updated spreadsheet and posted it to
our website
https://innovativepumps.com/calculators/Hydra-Cell-Pro-Pump-Horsepower-Calculator.htm;
it includes calculations for all Hydra-Cell Pump models, performs RPM
required calculations based upon drop-down CAM selection and otherwise
completely automates the horsepower calculations. I also added a feature
that calculates the maximum pressure available based upon the selected HP;
this assists with PRV selection and sometimes customers can accept slightly
less pressure associated with a lower HP.
We are not a commodity-based distributor, rather we leverage the unique
characteristics of Wanner Engineering’s sealless positive displacement pumps
to solve problems and enable our customers to meet their goals in the most
efficient manner possible, please keep us in mind for your next challenging
application!